Top supported units allowing free expansion at
the bottom.
Multi-fuel application.
Provision of reliable fulr feeding, controling,
distributing system.
Chevron drier with horizontal steam seperator
for high steam quality.
Attemperator with controls for maintaining
constant superheat temperature over wide range.
Furnace with membranewall construction (wherever
required).
Safety interlock & advanced system
of boiler instrumentation & control for safe operation,
monitoring & achieving higher efficiency.
Microprocessor based systems, PLC, DCS, SCADA
incorporated wherever required.
Easy access for each part.
High combution volume ensuring complete combution.
Tall combution chember.
Large grate area.
Automatic draft control.
APPLICATION
These boilers are suitable for burning
of either individual or in combination the fuels like coal,
oil, gas, rice husk, bagasse, biomass and other agricultural
wastes.
Coal firing units may require continuous ash discharge traveling
grate, where ash percentage is high. The coal with small ash
percentage and other solid fuels are successfully burnt on
dumping grate.
FURNACE
DIMENSIONS
Conservative rates of heat release, both
for combustion chamber and grate are selected for all fuels.
Grate dimensioning of furnace and arrangement of further heating
surfaces such as super heater, convention bank, economizer
and air heater run minimum risk of clogging, even in case
of over loading. The soot blowers, retractable and rotary
provided are sufficient to keep the surface clean for longer
period which is a requirement for boilers for co-generation.
SYMETRICAL
DESIGN
Box type combustion chamber uniform gas
velocity. The bank tubes are evenly placed, as a result, gases
leave the furnace at fairly uniform temperature. With the
feature;
Uniform evaporation across section.
Uniform water level in the drum
Uniform expansion of pressure parts is achieved. These
features result in quick response to rapid load swing, carry
high rating and produce dry steam at all
loads.
SUPERHEATER
For reducing superheater tube metal temperature,
the heating surface is divided in two section with counter
flow and parallel flow arrangements. The attemperator, to
control the steam temperature is, placed in interstage or
at the outlet, depending on the final steam temperature requirement.
LARGE
AIR HEATERS
Large Air Heaters are provided for higher
heat recovery and therefore higher efficiency. The hot air
assist combustion and makes furnace condition more suitable.
OVER
FIRE AIR SYSTEM
To reduce smoke and fly ash, over fire
air system is used. Over fire air burns vaporized volatile
matter which is in high percentage in Bagasse.
CINDER
RETURN SYSTEM
These are offered where improvement in
efficiency and operational ease is important, particularly
for large size boilers.
SPREADER
STROKER
Spreaders strokers for coal are mechanical,
where as for bagasse and similar fuels are pneumatic. These
are designed for suspension burning of lighter particles and
uniform distribution of fuel on the grate. Location of spreaders
are so decided that with minimum carry over of lighter particles
in suspension.
MAIN
FEATURES
Generators suitable for indoor and outdoor application.
Top supported units allowing free expansion at the bottom.
Multi-fuel application.
Provision of reliable fuel feeding, control and distributing
system.
Chevron Dryers with horizontal steam separator for high steam
quality.
Attemperator with controls for maintaining constant superheat
steam temperature over wide range.
Furnace with membrane wall construction. (wherever required).
Safety interlock and advanced system of boiler instrumentation
and control for safe operation, monitoring and achieving higher
efficiency.
Microprocessor based system, PLC, DCS, SCADA incorporated
wherever called for;
Easy access for each part.
High combustion volume ensuring complete combustion.
Inhouse manufacturing of important Auxillaries, such as deaerator,
multi cyclone dust collector, wet scrubber and soot blowers.
WE ALSO
OFFER FOLLOWING BOILER TYPES
Multi-fuel Boilers upto 150 T.
Pressures upto 110 ATA.
Super heater temperature upto 515ºC.
Pre-engineered shop assembled package boilers.
Drum internals consist of chevron driers
Andhorizontal Steam Separators. These internals are prefabricated
and bolted welded in the steam drum. Best performance is assured
over wide variation on of load. These work well during sudden
change in the load with normal boiler water conditions high
standard of steam purity is maintained.